Device power which connected to current transformers:
Maximum rated voltage:
720V
Typical application:
Indoor
Continuous operating current:
1,2xln
Test voltage per minute:
4kV
Security coefficient:
5
Rated primary current(In):
30A-5000A
Rated secondery current:
5A
Operating frequency:
50-60Hz
Operating temperature:
-5¡æ/+45¡æ
Thermal rated current:
1th=100xln (for MSQ-A type lth=60xln)
Dynamic rated current:
ldyn=2.5xln
Devices
Power(VA)
Ammeter Wattmeter Cos meter KWh-meter (active and reactive) Reactive power control units Overload relays Inverse current relays Secondary thermal relays
Ratio error of current tyansformers can be guaranteed between 100% and 120% of rated current. Error class can be 2-3 folding, especially the value of the under half rated current at the application, load current can be taken into consideration between In-1.2In
Power losses calculation fo cable:
P=I2sn¡Á2¦Ñ/S¡Á56(VA) ¦Ñ=cable length of secondary side(m) Isn =seconder rated current (A) S =cross section of cupper cable (mm2) P =power losses (VA) Example: Load connected to current transformer is one active and reactive kWh-meter with 4 m and 2,5 mm2 cable is 1+1+1, 43=3,43 VA.So it is necessary to use 5 VA current transformer.